LV433748

SKU: 168388
฿81,510.00
Moulded Case Circuit Breakers (MCCB), Compact NSX, NSX630HB2 ดูข้อมูลเพิ่มเติมได้ที่ Factomart.co.th
Sold-By: Factomart

Details

Details

Moulded Case Circuit Breakers (MCCB) Model :LV433748 Schneider Electric

Moulded Case Circuit Breakers (MCCB) - Schneider Electric - Compact NSX630HB2 - 3 Poles (3P3d) - Rated Current 500A (Electronic; Micrologic 6.3E-M)
- 630AF / 500AT - Short circuit breaking capacity (Icu) at (660/690Vac) 100kA

ข้อมูลสินค้า

Device short name
Compact NSX630HB2
 
Device application
Motor
 
Doles description
3P
 
[In] Rated current
500 A ( 65 °C )
630 A ( 40 °C )
 
[Ui] Rated insulation voltage
800 V AC 50/60 Hz
 
[Uimp] Rated impulse withstand voltage
8 kV
 
[Ue] Rated operational voltage
690 V AC 50/60 Hz
 
Breaking capacity code
HB2
 
Breaking capacity




100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 480 V AC 50/60 Hz conforming to NEMA AB1
100 kA at 600 V AC 50/60 Hz conforming to NEMA AB1
 
[Ics] Rated service breaking capacity


Ics 100 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
Ics 100 kA 525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 100 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
 
Trip unit technology
Electronic
 
Trip unit protection functions
LSIG
 
Trip unit rating
500 A ( 65 °C )
 
Protection type



Instantaneous short-circuit protection
Short time short-circuit protection
Ground fault protection
Overload protection (long time)
 
Control type
Toggle
 
Mounting mode
Fixed
 
Mounting support
Backplate
 
Complementary motor protection



Stalled rotor
Underload
Protracted starting time
Phase unbalance
 
Long time pick-up adjstment type Ir
Adjustable 9 settings
 
Long time pick-up adjustment range
250  -  500 A
 
Long time delay adjustment type
Adjustable
 
Thermal memory
20 minutes before and after tripping
 
Short-time pick-up adjustment type Isd
Adjustable 9 settings
 
Instantaneous pick-up adjustment range
6500 A
 
[Ig] Ground-fault pick-up adjustment range
100...500 A
 
Communication of data









Maximeters/minimeters
Time-stamped histories and event tables
Instantaneous and demand values
Thermal image function
Maintenance indicators
Demand current and power
Power quality
Energy metering
Protection and alarm settings
Phase sequence
 
Display type
LCD display
 
Type of measurement
Energy meter
 
Electrical data recording
Maintenance indicators
 
HxWxD
255x140x110 mm
 
Product weight
6.2 kg
 
Compact NSX  MCCB from Schneider electric